The Bluebook 5

CI/SfB

April 2014

(74)

Uniclass L721

Mainly used as a healthcare hospital mixer (TB H6). Demountable panel thermostatic mixer tap removable spout with interchangable filter and fitted with Armitage Shanks Bioguard. Markwik 21 proximity sensor mixer, demountable Medical and healthcare use Built in isolation valves Proximity sensor operation Front access for D-08 auditing and servicing Thermal disinfection feature Demount, submerge and disinfect

ARMITAGE SHANKS

Remove and sterlise spout BioGuard against bacteria Conforms to HBN 04-01 Addendum 2013 Illustrated A6244 Markwik 21 integral thermostat, demountable panel mixer, proximity sensor, Armitage Bioguard outlet fitted

Material Chrome Plated Metal

90

135

Weight 4.9kg

47

Ø62

Contract Brassware

Colour/Finish Chromium plated (AA) 90

52

261

135

13 - 27mm panel thickness

47

130

16°

Ø62

84

Standards Conforms to HTM64 (2006), HTM04, HFN30

150 - 200 *

127 Ø70

Ø48

52

13 - 27mm panel thickness

M33 x 1.5

Special notes This product is fitted with an Armitage Bioguard outlet which reduces the opportunity for bio film attachment and is lined with anti-microbial copper. Tap is activated by hand movement over the sensor and water will run for a predetermined length of time, factory pre-set at 1 minute but adjustable. Unique built-in thermal disinfection cleansing feature using kit S8239NU a bridging hose which is re-usable. A purging tool A4556AA is also available to facilitate initial installation or aid in system disinfection. * Line drawing shows recommended height over scrub up troughs. Flow rate regulated to maximun of 10 Litres per minute M33 x 1.5 130 Ø70 16° 250 max sensor detection zone 50 start of sensor detection zone * Refer to recommendations defined in HTM64

50 start of sensor detection zone

200

150 - 200 *

Ø48

250 max sensor detection zone

½” male

* Refer to recommendations defined in HTM64

½” male

261

90

135

47

Ø62

84

127

52

225

13 - 27mm panel thickness

130

16°

200

150 - 200 *

Ø70

Ø48

M33 x 1.5

50 start of sensor detection zone

250 max sensor detection zone

½” male

* Refer to recommendations defined in HTM64

5 : 5 : 3 : 15

Tel 0870 122 8822 Fax 0870 122 8282 Email info@thebluebook.co.uk Online search, specify & CAD: www.thebluebook.co.uk 225