The Bluebook 5

Brassware

CI/SfB

April 2014

(74)

Uniclass L721

Mainly used as a healthcare hospital mixer (TB H6). Demountable panel thermostatic mixer tap removable spout with interchangable filter and fitted with Armitage shanks Bioguard. Particulary suited for use with to Scrub up troughs. Markwik 21 time flow sensor mixer, demountable

ARMITAGE SHANKS

Medical and healthcare use Built in isolation valves Timed flow sensor operation Front access for D-08 auditing and servicing Thermal disinfection feature Demount, submerge and disinfect Remove and sterlise spout BioGuard against bacteria Conforms to HBN 04-01 Addendum 2013 Illustrated A6245 Markwik 21 integral thermostat, demountable panel mixer, time flow sensor, Armitage Bioguard outlet fitted

Material Chrome Plated Metal

261

Weight 5.8 kg

90

135

Contract Brassware 127

47

84

Colour/Finish Chromium plated (AA) 52

Ø62

13-27 panel thickness

200

Standards Conforms to HTM64 (2006), HTM04, HFN30

85 min

Ø48

Special notes This product is fitted with an Armitage Bioguard outlet which reduces the opportunity for bio film attachment and is lined with anti-microbial copper. Tap is activated by hand movement over the sensor and water will run for a predetermined length of time, factory pre-set at 1 minute but adjustable. Unique built-in thermal disinfection cleansing feature using kit S8239NU a bridging hose which is re-usable. A purging tool A4556AA is also available to facilitate initial installation or aid in system disinfection. * Line drawing shows recommended height over scrub up troughs. Flow rate regulated to maximun of 10 Litres per minute 250-300*

½” male

M33 x 1.5

50 start of sensor detection zone

120 sensor detection zone

14

39

225

16°

34

* Refer to recommendations defined in HTM64

90

135

47

Ø62

52

13-27 panel thickness

85 min

Ø48

250-300*

M33 x 1.5

50 start of sensor detection zone

120 sensor detection zone

14

39

16°

5 : 5 : 3 : 16

Tel 0870 122 8822 Fax 0870 122 8282 Email info@thebluebook.co.uk Online search, specify & CAD: www.thebluebook.co.uk

34

* Refer to recommendations defined in HTM64

Made with